MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Backflow Preventer on Discharge Side of Pump?

2/19/2019

12 Comments

 
Is there any benefit to having the backflow preventer on the discharge side of the fire pump? We've seen several RFPs recently that are requiring the backflow to be on the discharge side of the fire pump.

To me it seems as though this arrangement unnecessarily leaves more pipe and mechanical components exposed to the public water supply, but I'd be interested in others' opinions.

Posted anonymously by a member for discussion. Discuss this  | Subscribe
12 Comments
Brian Gerdwagen FPE
2/19/2019 10:08:35 am

This seems to be a hold-over from an older version of UFC 3-600-01. The newer versions do not require this and defer to NFPA 20.

Reply
JOE MEYER
2/19/2019 10:42:02 am

Where I've seen it - it has been military requirements for the backflow to be on the discharge side, but only required on a specific project. As you've mentioned UFC 3-600-01 doesn't require this arrangement.

Reply
James
2/19/2019 10:11:59 am

From my experience, almost every water utility company will require a backflow device at the incoming service location after the house control valve. I would imagine not having one until after the fire pump be a big "no-no".

Reply
James
2/19/2019 10:14:24 am

Ah I might have misread what you asked. Is this a BFP that is additional to the one at the incoming service? I personally have never installed a BFP after a fire pump, just single check valves as per NFPA 20 diagrams.

Reply
Pierre Lemieux link
2/19/2019 10:14:46 am

There is only one probable answer to this that I can think of.
As the backflow preventer springs create a pressure drop across checks #1 & #2, this may cause vortexing or cavitation and lower the availablbe npsh.

Reply
PETE
2/19/2019 11:35:17 am

PIERRE- The backflow pressure drops are consistent with their listings. Any instantaneous cavitation that may occur on pump-run, is addressed in NFPA 20 with a 10 x suction nominal diameter distance upstream of the pump suction flange to the backflow discharge.

Reply
Franck Orset
2/19/2019 10:36:07 am

As it has been said, a check valve is necessary on the discharge side of a pump.
A backflow preventer (large device), is normaly required at the connection from the city water supply to your sprinkler system, if you have a booster pump. This is mostly to avoid a "pollution" of the city system from the sprinkler system.
In that case, you might have the "backflow preventer" at the suction side and there is no need to add another one on the discharge side (but you still need the check valve).

Reply
C.T. Carbonari link
2/19/2019 12:40:17 pm

Backflow Prevention Assemblies (BFPA), by definition, protect the potable water supply from contaminants. Ref: Manual of Cross-Connection Control developed by the Foundation for Cross-Connection Control & Hydraulic Research.

BFPAs are categorized into (2) Classifications. Those that protect against Health Hazards (RP, RPDA, PVB) and those that protect against Non-Health Hazards (DC, DCDA).

(Typically, Firelines use Dector Assemblies (BFPAs with a 3/4" By-Pass Assembly) to monitor any and all flow below 3 gpm.)

Installing a BFPA on the discharge side of the pump (without an additional BFPA upstream of the system) would defeat this purpose.

To answer the original question: The only "Benefit" I see to downstream installation would be the psi savings you would get on the suction side of the pump due to not having to account for the headloss across the BFPA on the supply side of the flow curve. Or, possibly, installing downstream due to difficulty in adhering to 10 Pipe Diameters of straight pipe on Pump Suction.

This has been one of the more interesting questions I've read on MeyerFire and I enjoy everyone's insights. I learn a lot from others through these posts.

On a side note: The City that I do a lot of work in has recently ammended their code requirements to mandate installation of an RPDA on Fire Protection Systems for High Rise Buildings. How the Fire Protection System for a High Rise Building introduces a potential Health Hazard to the City Water Supply (whereas a Low Rise does not) is a complete mystery to me. Any insights would be appreciated. There is no such thing as a "greater" or "lesser" degree of protection with BFPAs.

Reply
J. Diaz
2/19/2019 03:40:00 pm

This is one of the "suggestions" from Factory Mutual. Depending on the reviewer, it could be seen as the only approved installation method. Generally, they are open and could accept the conventional way.

See data sheet 3-07 Section 2.3.1.7 and 2.3.1.8

2.3.1.7 Do not install a device or assembly (including, but not limited to backflow prevention devices or
assemblies) that will stop, restrict starting, or restrict the discharge of a fire pump or pump driver in the suction
piping.
2.3.1.8 Locate backflow preventers on the discharge side of the fire pump whenever possible, due to the
increased friction loss and the potential negative effect on pump performance.

As per your specific question, I agree with others. There's no benefit; it is indeed detrimental since in that arrangement, the pump itself (mechanical equipment requiring maintenance or possible replacement) may be the culprit of contamination of a municipal systems. Most cities prefer to have the BFP as close as possible of the city mains.

Reply
Ed Glynn
2/19/2019 05:48:00 pm

There is an issue where the sole source of potable water is strictly a tank that has head pressure only.

It would not be a "traditional" potable source but a potable water source nonetheless.

As a result of head pressure only, the checks would not have enough pressure to open therefore a positive displacement pump would be required and a backflow on the discharge side of the fire pump.

Reply
Todd Delisle
12/24/2020 10:23:03 am

NFPA does not require the installation of BFPs.

BFPs are a requirement established to protect potable water systems.

I don't know of any fire pump listed for use on potable water; or properly safeguarded to prevent back siphoning through its appurtenances.

Reply
Eric
9/8/2021 05:45:04 pm

Ive read thru these comments and it makes much more sense to me to locate the backflow on the suction side of the pump. However, I have recently run across a facility with the backflow down stream of the pump. The main fire pump controller is connected between the the first check valve and the backflow preventer. The jockey pump line is connected after the backflow preventer. Heres the problem: when the first check valve fails the main fire pump continuously starts & stops because h the pressure is bleeding off they the relief valve while the jockey pump remains idle. Is this an acceptable scenario?

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Feb 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 30B
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT