MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Backflow Preventer on Discharge Side of Pump?

2/19/2019

11 Comments

 
Is there any benefit to having the backflow preventer on the discharge side of the fire pump? We've seen several RFPs recently that are requiring the backflow to be on the discharge side of the fire pump.

To me it seems as though this arrangement unnecessarily leaves more pipe and mechanical components exposed to the public water supply, but I'd be interested in others' opinions.

Posted anonymously by a member for discussion. Discuss this  | Subscribe
11 Comments
Brian Gerdwagen FPE
2/19/2019 10:08:35 am

This seems to be a hold-over from an older version of UFC 3-600-01. The newer versions do not require this and defer to NFPA 20.

Reply
JOE MEYER
2/19/2019 10:42:02 am

Where I've seen it - it has been military requirements for the backflow to be on the discharge side, but only required on a specific project. As you've mentioned UFC 3-600-01 doesn't require this arrangement.

Reply
James
2/19/2019 10:11:59 am

From my experience, almost every water utility company will require a backflow device at the incoming service location after the house control valve. I would imagine not having one until after the fire pump be a big "no-no".

Reply
James
2/19/2019 10:14:24 am

Ah I might have misread what you asked. Is this a BFP that is additional to the one at the incoming service? I personally have never installed a BFP after a fire pump, just single check valves as per NFPA 20 diagrams.

Reply
Pierre Lemieux link
2/19/2019 10:14:46 am

There is only one probable answer to this that I can think of.
As the backflow preventer springs create a pressure drop across checks #1 & #2, this may cause vortexing or cavitation and lower the availablbe npsh.

Reply
PETE
2/19/2019 11:35:17 am

PIERRE- The backflow pressure drops are consistent with their listings. Any instantaneous cavitation that may occur on pump-run, is addressed in NFPA 20 with a 10 x suction nominal diameter distance upstream of the pump suction flange to the backflow discharge.

Reply
Franck Orset
2/19/2019 10:36:07 am

As it has been said, a check valve is necessary on the discharge side of a pump.
A backflow preventer (large device), is normaly required at the connection from the city water supply to your sprinkler system, if you have a booster pump. This is mostly to avoid a "pollution" of the city system from the sprinkler system.
In that case, you might have the "backflow preventer" at the suction side and there is no need to add another one on the discharge side (but you still need the check valve).

Reply
C.T. Carbonari link
2/19/2019 12:40:17 pm

Backflow Prevention Assemblies (BFPA), by definition, protect the potable water supply from contaminants. Ref: Manual of Cross-Connection Control developed by the Foundation for Cross-Connection Control & Hydraulic Research.

BFPAs are categorized into (2) Classifications. Those that protect against Health Hazards (RP, RPDA, PVB) and those that protect against Non-Health Hazards (DC, DCDA).

(Typically, Firelines use Dector Assemblies (BFPAs with a 3/4" By-Pass Assembly) to monitor any and all flow below 3 gpm.)

Installing a BFPA on the discharge side of the pump (without an additional BFPA upstream of the system) would defeat this purpose.

To answer the original question: The only "Benefit" I see to downstream installation would be the psi savings you would get on the suction side of the pump due to not having to account for the headloss across the BFPA on the supply side of the flow curve. Or, possibly, installing downstream due to difficulty in adhering to 10 Pipe Diameters of straight pipe on Pump Suction.

This has been one of the more interesting questions I've read on MeyerFire and I enjoy everyone's insights. I learn a lot from others through these posts.

On a side note: The City that I do a lot of work in has recently ammended their code requirements to mandate installation of an RPDA on Fire Protection Systems for High Rise Buildings. How the Fire Protection System for a High Rise Building introduces a potential Health Hazard to the City Water Supply (whereas a Low Rise does not) is a complete mystery to me. Any insights would be appreciated. There is no such thing as a "greater" or "lesser" degree of protection with BFPAs.

Reply
J. Diaz
2/19/2019 03:40:00 pm

This is one of the "suggestions" from Factory Mutual. Depending on the reviewer, it could be seen as the only approved installation method. Generally, they are open and could accept the conventional way.

See data sheet 3-07 Section 2.3.1.7 and 2.3.1.8

2.3.1.7 Do not install a device or assembly (including, but not limited to backflow prevention devices or
assemblies) that will stop, restrict starting, or restrict the discharge of a fire pump or pump driver in the suction
piping.
2.3.1.8 Locate backflow preventers on the discharge side of the fire pump whenever possible, due to the
increased friction loss and the potential negative effect on pump performance.

As per your specific question, I agree with others. There's no benefit; it is indeed detrimental since in that arrangement, the pump itself (mechanical equipment requiring maintenance or possible replacement) may be the culprit of contamination of a municipal systems. Most cities prefer to have the BFP as close as possible of the city mains.

Reply
Ed Glynn
2/19/2019 05:48:00 pm

There is an issue where the sole source of potable water is strictly a tank that has head pressure only.

It would not be a "traditional" potable source but a potable water source nonetheless.

As a result of head pressure only, the checks would not have enough pressure to open therefore a positive displacement pump would be required and a backflow on the discharge side of the fire pump.

Reply
Todd Delisle
12/24/2020 10:23:03 am

NFPA does not require the installation of BFPs.

BFPs are a requirement established to protect potable water systems.

I don't know of any fire pump listed for use on potable water; or properly safeguarded to prevent back siphoning through its appurtenances.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About