For an R-4 occupancy, Sections 420.2 and 708 require fire partitions, including the continuity requirements of Section 708.4. Section 903.2.8 requires sprinklers and permits NFPA 13D under certain R-4 conditions.
If NFPA 13D is permitted, can attic sprinkler protection be used in lieu of extending the required fire partitions to the underside of the roof, or are both requirements still applicable? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Chris
10/5/2026 08:48:21 am
See Section 708.4, Exception 2.2, which only references NFPA 13 or NFPA 13R sprinkler systems for use of the exception that you are describing.
Reply
Streeter
10/5/2026 10:25:03 am
As Chris said, you would have to sprinkle the entire building as a 13 or 13R to no extend the partition to the roof deck.
Reply
Jack G
10/5/2026 02:05:47 pm
I agree with both. Per chapters 717, 718,
Reply
Jack G
10/5/2026 02:11:51 pm
Extending sprinklers into the affected areas and calculating the system under 13d, would not supply the system with the water required for an NFPA 13 system, so the AHJ should rein in.
Reply
Jack G
10/5/2026 02:31:26 pm
Also in chapter 5 of the IBC, in there were height increases taken for sprinklers only a 13 system can be installed ( up to 3 story, 12 k sq ft ) .
Reply