MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Are Separate Fire & Domestic Lines Required?

6/17/2025

7 Comments

 
Do I need a separate 6" fire line to a building sprinkler system, and a second water line for all other uses?

This is for an NFPA 13 system. ​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
Chad
6/17/2025 07:26:25 am

Depends on the water company/department plus the sections below (2019 NFPA 13) As long as it calcs out, it could be shared. The domestic demand is required to be accounted for. Same for 13R and D, although D uses a fixed 5GPM domestic demand


For a full 13 system typically, yes its a dedicated main regardless of the calcs due to water department regs.


5.1.3.1
Except as provided in 5.1.3.2 or 5.1.3.3, no pipe smaller than 6 in. (150 mm) in diameter shall be installed as a private service main.

5.1.3.2
For mains that do not supply hydrants, sizes smaller than 6 in. (150 mm) shall be permitted to be used subject to the following restrictions:
(1)
The main supplies only automatic sprinkler systems, open sprinkler systems, water spray fixed systems, foam systems, or Class II standpipe systems.

(2)
Hydraulic calculations show that the main will supply the total demand at the appropriate pressure. Systems that are not hydraulically calculated shall have a main at least as large as the system riser.


Enhanced Content
Collapse
Private fire service mains must be at least 6 in. (150 mm) in diameter where they supply hydrants. In some cases, the use of a minimum 8 in. (200 mm) pipe for dead-end mains is advised. Where the fire service mains do not supply hydrants, they are permitted to be sized based on hydraulic calculations, or they are permitted to be as large as the riser under certain conditions. Fire mains need a water supply sufficient to meet the demands of the sprinkler systems, inside hose, outside hose, and other anticipated water demands.

5.1.3.3


Where a single main less than 4 in. (100 mm) in diameter serves both fire systems and other uses, the non-fire demand shall be added to the hydraulic calculations for the fire system at the point of connection unless provisions have been made to automatically isolate the non-fire demand during a fire event.

Enhanced Content
Collapse
Simultaneous flow of the non-fire water and automatic sprinkler systems must be considered when small diameter [i.e., less than 4 in. (100 mm)] combination lead-ins are used. The additional non-fire waterflow can create increased friction loss, resulting in a reduction in the water available for the sprinkler system.

The term domestic was replaced with non-fire in the 2013 edition. This change was made to emphasize that any water that is flowing needs to be accounted for whether it is being used for domestic use or other uses.

Reply
Anthony
6/17/2025 08:16:21 am

Depends on the municipality. In some areas its common to have separate lines so the water authority can shut off your domestic water for non payment and not have your building burn down.

Per NFPA 13 you can definitely use a combined 6'' incoming line and its very common to do so. I would suggest adding a 'master' OS&Y often called a city valve so the building water can be shut off from the main water entry point w/o having to mess about with a road box.

Reply
Jesse
6/17/2025 08:17:17 am

Yep you can, but there are some pitfalls. I recently had a project in Houston where there was an existing fire line and RPZ. Everything calc'd and was though fine until we were told that the domestic demand, or non-fire water was also coming off of that same fire line. So we had to add additional backflow preventers to the risers in each building which killed our calcs.

So while you can do it, it doesn't always work out for the best. Most of our Austin metro projects have separate domestic / fire taps.

Reply
Glenn Berger
6/17/2025 08:26:49 am

It depends on your locality and their regulations. Also check with the Owner's Parties having interest on the project as they may have additional requirements.

NFPA 13 does not require a dedicated supply pipe into the building.

Reply
Dan Wilder
6/17/2025 09:06:40 am

Not a requirement and others have given some good feedback above.

One of the biggest drawbacks I have found when this is proposed is the fact that cross contamination becomes a big deal. Differing pipe type requirements to comply with AWWA requirements (C.L.D.I.P, Copper), the addition of a RPZ, and non-fire GPM allowances creates a heavy toll on available flow and pressure.

Reply
Jack G
6/17/2025 09:35:31 am

It’s probably for most public utilities that separate dedicated lines are required so if you don’t pay your water bill ( and they shut you down) your building still has fire protection. This is prevalent for water companies in my jurisdiction.

Reply
Mark
6/17/2025 01:42:30 pm

I am an AHJ for a local municipality in Illinois, and the municipality requires a combination main into the fire protection/meter room which then is teed to the separate mains. The plumbing inspectors have explained to me that this is a State requirement in the Plumbing Code to avoid cross-contamination of the municipal water distribution system and dead-end mains.

The explanation they have given me is that a separate fire protection main does not have backflow protection until in the building before the fire pump or riser and since the fire protection water is not regularly flowed this will create a stagnant water situation and a large dead-end main the length from the municipal water main to the fire protection system. The Plumbing Code limits dead-end mains to 2' maximum, so this installation creates a hazardous situation with no cross-connect protection to the municipal water main.

This applies to all occupancy types, and we further require RPZ's, not DDC, on any fire sprinkler system with an FDC or other possibility of contamination. The sprinkler systems are calc'd to include both domestic and fire protection system demands.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Feb '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT