We have a climbing gym that's in construction. See the image below. The architect is calling this out as an assembly space, so we have light hazard upright protection up at the roof only. The fire marshal walked the building and has concerns that the climbing walls create obstructions. Are the climbing walls a construction concern? Any other input here?
Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Pete H
7/12/2022 06:51:39 am
Seems like a floor mounted obstruction if it goes up high enough. I'd say as long as you're following Table 8.6.5.2.2 (NFPA 13 2016 Edition) you're okay. So as long as there are more than 18" vertical distance between the deflector and the top of the climbing walls, I wouldn't worry about your horizontal distance to the wall or your spacing.
Reply
Alex
7/12/2022 07:43:21 am
Hi,
Reply
schulman
7/12/2022 08:05:33 am
anything that leaves a large enough area of the floor without water during a fire is an obstruction
Reply
Jesse
7/12/2022 08:11:03 am
We just did a very large project like this and dealt with this same issue.
Reply
Franck
7/12/2022 08:17:08 am
Not a technical point of view (it has been highlighted above), but a practical point of view : is the climbing wall combustible? Is there something at the bottom of the wall combustible? If the answer is no to both questions, then what is the problem? Your ceiling sprinklers would cover a “no hazard” area…
Reply
Dan Wilder
7/12/2022 08:27:12 am
Most times, just the vertical portions aren't an issue.
Reply
Glenn Berger
7/12/2022 08:42:11 am
Climbing walls are a vertical obstruction as defined by NFPA 13. My experience is that if there is sufficient clear space on the top of the climbing wall, then sprinkler protection does not require modifications.
Reply
Greg
7/19/2022 08:54:09 am
In one of my experiences with climbing walls, the position of the wall against a interior hallway wall created a void space. The space was used for storage of ropes and climbing gear. It was large enough to enter through a small hatch door and included a light switch and light. The interior of the climbing wall was a resin. A sprinkler was extended into the space and I believe we included a wall recessed valve to isolate. The wall valve was labeled. This was a work-around achieved following a preliminary occupancy walk-through when the space was discovered.
Reply
Tracy
9/10/2024 02:45:58 pm
What about the crash pads? Does anyone know if the crash pads push the combustibility load out of light hazard or if they required to have a fire resistance rating?
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop November '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
December 2024
PE PREP SERIES |