NFPA 13 required Extra Hazard Group I sprinkler protection for Aircraft Hangars.
What is the appropriate density/area be under CMDA design? NFPA 409 has a minimum density of 0.17 gpm/sqft (6.9 Lpm) and uses k5.6 to k8.0 quick response sprinklers, however the design area is 15,000 sqft (1,394 sqm). The hanger is only 9,680 sqft (900 sqm) and three light aircraft are to be stored in the hangar. Would 0.30 gpm/sqft (12.2mm) density and an area of 2,500 sqft (230 sqm) with quick response not be more affective than 0.17 gpm/sqft (6.8mm) density and a 9,690 sqft (900 sqm) area? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
M. Newell
7/14/2022 08:11:15 am
If you look at it solely from a discharge perspective.
Reply
franck
7/14/2022 11:53:31 am
Note that this calculation only applies when different adjacent occupancies with different required densities (or different type of k-factor for the sprinklers) are present : i.e. you want to meet .3 over 2500 over a 2500 sq ft area only, but require .17 over 15 000 sq ft for the remaining area.
Reply
Jesse
7/14/2022 08:25:41 am
I'm confused. Are you protecting the hangar under 13, or are you protecting the hangar under 409?
Reply
Anthony
7/14/2022 08:27:11 am
I believe the AHJ/building code would tell you which standard takes precedent and thus which curve to use.
Reply
Dan Wilder
7/14/2022 08:41:18 am
Need to identify the type of hangar first before deciding on a design approach.
Reply
Eric
7/14/2022 10:33:36 am
Dan's point about horizontal fire spread is really important here.
Reply
franck
7/14/2022 11:44:36 am
EH gr 1 only applies to hangars that are not under 409 requirements
Reply
Tim
7/15/2022 04:54:16 am
Now I see the role of the automatic water sprinklers is clearly to cool other risks in the space. Fire suppression has to be low level in form of LX or MX foam. High density application from the roof will possibly have negative impact on the foam blanket. Its clear now why the lower density 0.17 over 5000 sqft for Type 2 (000) construction is recommended by NFPA 409. Design and hydraulics NFPA 13 the density and area NFPA 409. Low level suppression is a must do if you want to have any hope in successful automatic fire suppression or intervention.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop November '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
January 2025
PE PREP SERIES |