Question in relation to ESFR sprinklers. Per NFPA 13 2016 Section 8.12.5 - obstructions 12" to 24" wide, the sprinkler must be 2 feet away.
There is no specific code for obstructions larger than 24"; does this mean these obstructions would always require coverage beneath? I ask because I have a 36" cable tray - if it's centered between two branch lines, can I apply the code to half the obstruction? In this case, the head would be further than 2' from 18" of the obstruction on both sides. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments
Glenn Berger
11/12/2025 08:28:44 am
In the 2016 version of NFPA 13 Section 8.12.5.3 appears to be applicable to this scenario. And yes sprinklers most likely would be required based upon specific criteria contained within the section.
Reply
Chad
11/12/2025 08:45:00 am
This is the applicable section from 2019 regarding ESFR continuous obstructions below, like a cable tray,
Reply
Jesse
11/12/2025 10:11:17 am
The ESFR obsturction rules are pretty stringent and it seems the more recent iterations of 13 made is less clear than before. I agree with Glenn and Chad that you'll need protection beneath the cable tray
Reply