MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • JOIN
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Add Fire Pump and Keep Manual Wet Standpipe?

9/30/2019

5 Comments

 
Can I add a fire pump to my combination Manual wet standpipe and sprinkler system and still use a manual wet standpipe?

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments
Casey Milhorn link
9/30/2019 10:23:56 am

Yes, your fire pump is sized only for the greatest sprinkler demand. Be careful that your pipe sizing through the pump and around the bypass meet the larger demand. A calculation should really be performed on the manual wet standpipes using the local responding fire departments standard pressure from the pumper truck (usually 150 psi from my experience, more if the building is taller). This is how you should determine your standpipe sizing, or in whatever method is approved by the AHJ. For example, if your sprinkler demand is fairly low in GPM, you might be able to get by with 4" or less of suction, discharge, and bypass piping, but that doesn't mean that 4" is enough for the manual wet standpipe demand. Hope that helps.

Reply
ColinLusher link
9/30/2019 04:10:26 pm

Unless I"m misunderstanding you, I must respectfully disagree with this response. In no situation (that I am aware of) would your FDC be upstream of your fire pump suction. Therefore, your fire pump pipe size and bypass size would have no affect on a manual standpipe downstream of the fire pump. You would just need to insure that the FDC, which should be connected downstream of your fire pump check valve, was at minimum, the same size as your Manual Standpipe.

For example, if you have a manual wet standpipe system combined with an automatic wet pipe fire sprinkler system, and a fire pump serving ONLY the fire sprinkler portion of the system, then you could install a 4" fire pump/bypass even if your MANUAL standpipe system piping was required to be 6"....you'd just need to insure that all FDC piping downstream of your fire pump was sized per the highest demand, in this case, the 6" manual standpipe system. When the fire dept pumps through your FDC, flow will not go through the fire pump system piping so the fire pump pipe size is not relevant to the manual standpipe system flow demand.

Let me know if I'm missing something here....

Reply
Casey Milhorn
9/30/2019 05:07:06 pm

Yeah, I shouldn't have said the suction sizing. I'm talking more if the FDC is tied into the bypass piping. The bypass piping, and anything downstream of the FDC should be sized with the manual wet standpipe in mind. Thanks for the correction.

Pari
9/30/2019 01:20:52 pm

Yes, you can do that as long as the system is not serving high rise building.

Reply
Colin Lusher
9/30/2019 03:59:40 pm

This depends on the building height and your AHJ. If your building is classified as a high rise, then NFPA 14 requires an Automatic standpipe system, however, when retrofitting an existing non-sprinklered high rise building with an automatic sprinkler system, many jurisdictions will allow the standpipe system to remain "manual". In this situation for example, in my jurisdiction, the AHJ allows us to convert the existing dry standpipe system to a manual wet system; the old dry standpipes service the new sprinkler system, but we size the pump only for the fire sprinkler system, and the standpipe demand must be met by the fire department at the FDC.

If your building is NOT a high rise, then the manual system should be fine as this is allowed by NFPA 14...but I'm guessing you're talking about a high rise?

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​May 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    Aba
    Ada
    Asce-7
    Asme-a171
    Astm-e1354
    Daily Discussion
    Design-documents
    En-12845
    Explosion-protection-prevention
    Fire-detection-and-alarm-systems
    Fire-dynamics
    Flammable-combustible-liquids
    Fm-global
    Human-behavior
    IBC
    Icc500
    IFC
    Imc
    Ipc
    Irc
    Iso
    Means Of Egress
    Nbc
    Nfpa-1
    Nfpa-10
    NFPA 101
    Nfpa-101
    Nfpa-11
    Nfpa-110
    Nfpa-1142
    Nfpa-1221
    NFPA 13
    Nfpa-13
    NFPA 13D
    Nfpa-13r
    NFPA 14
    Nfpa-15
    Nfpa-16
    Nfpa-17a
    Nfpa-20
    Nfpa-2001
    Nfpa-214
    Nfpa 22
    Nfpa-220
    Nfpa 24
    Nfpa-241
    Nfpa-25
    Nfpa-25
    Nfpa-291
    Nfpa-291
    Nfpa-30
    Nfpa-30b
    Nfpa-33
    Nfpa-400
    Nfpa-409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • JOIN
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT