MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

A Code Call List - Questions for Designers & AHJs

12/3/2025

14 Comments

 
One of the things I feared most when I had my first real job was that I was going to be exposed as a complete fraud.

Yes, I had a degree. That degree had a grand total of 9 credit hours specifically to fire protection, which statistically is more than roughly 90% of our industry starts out with.

But, see, the problem was… that I knew nothing.

I knew this.

But my fear was that when I made my first phone call to someone on the other line, they’d quickly know this too.

​And that all came in the form of my first ‘code call.’

THE CODE CALL
We used the term code call, I don’t know what you might call it, but it’s just a touchpoint check in with the AHJ to be sure that (1) we’re on the right track with applicable codes and standards, and (2) that we coordinate jurisdictional needs.

What good is a set of engineering bid plans, if we halfhazardly threw an FDC in the wrong spot? Or the fire alarm control panel? If we referenced the wrong codes? If we stipulated too low of a hydraulic safety factor? If we located the hose connections on the wrong landings?

The answer is no good at all. If we’re not helping clarify and coordinate the needs of the project with the jurisdiction, then we, as consultants, are simply getting in the way and making things more difficult than they need to be.

IMPOSTER SYNDROME
​Back to that phone call.

How long would it take for the person on the other line to realize that I knew very nearly absolutely nothing about fire protection?

That if they asked one clarifying question, it would call my bluff and I’d have no escape? Ten seconds? Twenty seconds? It wasn’t an irrational fear, nor was it overwhelming.

I made that call. And more after it. And I did make a fool of myself. I once asked “do you require duct detectors to be located on the supply side, return side, or per code?”

The response: “Why would it be anything other than per code?”

Ope. Game’s up. I have no idea. Time to pack the bags and find a new career.

 
All drama aside, I survived. Sometimes failed. I learned. I slowly grew to understand the purpose behind our list of questions.

Who were these people I was calling?

That’s half the game. Sometimes it’s a Fire Marshal. Sometimes it’s a plan review as part of the building department. Or fire department. Sometimes it’s the volunteer combination of Fire Chief/Marshal/Inspector/Reviewer.

Sometimes they were the nicest people I’ve ever met. Sometimes hostile. Just goes with the territory.

I’ve had jurisdictions that wouldn’t pick up the phone unless I called from a local area code. And I’ve had others apologize because they wouldn’t be able to run a flow test for me until Monday morning. (I had called on a Friday. At 4:45pm). 

Diatribe aside, I’d like to share the list of questions that I ask – (1) – so you can critique and help us all improve upon the list of questions – and (2) – so that future generations of inexperienced callers might not have to suffer the imposter syndrome that I did with those first few calls.

WHO IS THIS FOR?
Here is my developed list of questions that I would ask today for a code call. This is very specifically used for consultants to coordinate requirements with AHJs before a bid set is issued.

Why isn't this used for contractors? Would I ask this when doing shop drawings?

No; I might coordinate FDC types and locations. Coordinate standpipes. Coordinate some fire alarm or waterflow questions. However, a designer at the shop drawing stage is not the person to determine the scope. They can and should coordinate, but not determine scope.

A consultant's role is to determine the scope, so principally these questions are supposed to happen before bids ever take place. These do have cost impacts.

MY LIST OF QUESTIONS (AND NOTES)
Below it is a very short  context for why I ask the question. Code basis can wait for now. This is long enough as is.

What I ask from you is what you would tweak?

If you’re an AHJ, how can I better ask the question?

How can I better clarify the intent of the question?
 
OPEN-RESOURCE FOR CODE CALLS
We’re actively working on an open and free tool just for code calls. Some time ago we tried a spinoff code call database, but the enthusiasm for jurisdictions to volunteer information wasn’t something that we could get to scale.

So I’d like to try this from a different angle.

My hope is that, if we construct this open tool right, and educate around the process in the open, it could be a tremendous resource for both designers and AHJs to meet in the middle and have coordinated projects that meet the needs of each jurisdiction.

Easier and better results, every time.
Picture
A new code call resource for designers and AHJs to better coordinate local requirements is in the works.
So, here’s the list of questions that I would ask today, almost like a script.

My own personal notes are italicized below each question.
 
BRIEF INTRO
Thanks for taking my call. I’m Joe Meyer, designing the [project] at [address]. It’s going to have [fire alarm/sprinkler/standpipe system(s)], and I’d like to ask you a few questions to make sure we’re coordinated with your department. Should take about five minutes. Is that OK?
  → Note: If the time isn’t good, or they’d prefer an email, I’d go that route instead.
 
APPLICABLE CODES & STANDARDS
1. Great. Your website says you’ve adopted the [2012/2015/2018/2021/2024 IBC or NFPA 101], is that correct?
  → Note: Doing the research ahead of time is key. Without it, it makes the listener feel like they’re doing the work.
 
2. Do you adopt any specific editions of NFPA standards like NFPA 13, 14, or 72, or just whichever edition is referenced by your building code?
  → Note: Many people don’t know this, but IBC Chapter 35 and NFPA 101 Appendix D or E will actually list which editions of NFPA standards are referenced. Some jurisdictions will adopt very specific editions, which is why I like to ask the question here.

Following questions noted with an asterisk (*) are only asked if necessary.

FIRE ALARM*
3. For fire alarm, we intend to locate the main control panel in [front entry/main electrical room/a back of house area]. If we do so, do you require an annunciator panel at the building’s front entry?
  → Note: For small buildings with one main entry where the FACU is located near the entry, no annunciator is usually needed. For larger or more complex buildings, when we might not want the FACU at the front entry, having an annunciator at the front is a very reasonable need.
 
4. Does the fire alarm monitoring require a listed Central Station Service, or is standard code-required monitoring, like a supervising station, acceptable?
  → Note: Jurisdictions that require a listed Central Station service usually know what it is, and will recognize that it’s required. It’s more expensive and carries more stringent requirements than a normal supervising station, which is a code-minimum requirement.
 
DUCT DETECTION*
5. When duct detectors are needed, do you simply require locations to be per [the IMC/NFPA 90A], or do you require duct detectors to be located in specific locations, like the supply or return side of units in the ductwork?
  → Note: This is a question I could use help with. A simple ‘per code’ answer is wanted here, but some jurisdictions have insisted on locating duct detectors on the supply-side of units, or return-side, or both. If the jurisdiction has a specific requirement, I’d like to know that now rather than be surprised later, but most usually don’t, and as a result, it’s a lame question to ask in those cases.
 
6. Do you require duct detectors to initiate an alarm signal, or is it OK to have those report a supervisory signal to the fire alarm control panel?
  → Note: NFPA 72 allows duct detectors to initiate a supervisory signal, because they’re more prone to nuisance alarms than other devices. An alarm signal usually results in a truck rolling up to the building each time. Jurisdictions that are familiar with this topic are usually more than happy to have duct detectors on supervisory rather than alarm.
 
7. When a duct detector activates, can it shut down just that unit or do you require all units to be shutdown?
  → Note: To my understanding, this is just a preference. Not a huge deal either way unless we’re talking about a massive building or building complex where all units shutting down would be very uncomfortable and problematic.
 
SECURITY / KNOX BOX
8. Do you require a Knox Box?
  → Note: There’s likely a code path for this, but it’s not something I’ve hunted down to date. Most jurisdictions can readily answer this.
 
9. Is the Knox Box required to tie to the fire alarm system?
  → Note: These can be monitored by the fire alarm system. Most jurisdictions don’t require them to be monitored, but some will in areas that have higher crime rates.
 
FIRE SUPPRESSION - FIRE DEPARTMENT CONNECTION*
10. Do you mandate a maximum distance from a fire department connection to a nearest hydrant?
  → Note: Some jurisdictions care, others less so. There’s (to my knowledge) not a mandated distance, but some jurisdictions will require as close as 50 ft and others as far away as 400 ft.
 
11. Can the FDC be mounted on the building’s street-facing exterior wall, or does it have to be located remotely from the building?
  → Note: As a designer, my strong preference is to have the FDC on the building to save cost, protect the pipe from freezing, protect the pipe from mechanical damage, keep it clear from snow, and keep it easier to inspect, maintain, or repair. Operationally, depending on the building and the site, some departments are not going to want to send firefighters to the building face and would rather have a remote connection for some applications.
 
12. What type of FDC do you use [Dual-Inlet 2-1/2” / 4” Storz / 5” Storz]?
 
13. Do you require locking caps on the FDC?
  → Note: Some jurisdictions will have locking caps to prevent people from shoving debris, trash, or other ‘items’ into FDCs, and to prevent theft of the caps. Many areas have no need for locking caps.
 
BACKFLOW*
14. What type of backflow preventer do you require [double check, double check detector, RPZ, or RPZ detector]? We [will/will not] have antifreeze or chemical additives in the system.
  → Note: Some jurisdictions, like fire departments, may not want to answer this because it’s under the building or water department. But most are familiar with the requirements anyways. Some places require RPZs for everything fire protection (like an Illinois state mandate). By code, RPZs are required if an antifreeze system is used, or if chemical additives are added to the system (such as corrosion inhibitors like Vapor Pipe Shield).
 
15. We intend to locate the backflow inside the building. Is this acceptable?
  → Note: This is a designer preference for longevity of the backflow, protection from damage and tampering, protection from freezing, service, maintenance, and cost. Some owners may want the floor space or jurisdictions might require it to be outside (though I don’t know why).
 
16. [If a double check is allowed, allowed to be inside, and there is only a single zone] We intend to use a backflow preventer that’s listed for a vertical orientation. Is it acceptable to install it vertically?
  → Note: RPZs have to be horizontal. If we have single-zone systems, designers generally prefer to use a ‘shotgun’ approach and save floor space. This is usually fine.
 
HYDRAULICS*
17. Do you mandate a safety factor for fire sprinkler systems?
  → Note: This is a topic that is book-worthy. NFPA 13 has no mandate other than to account for seasonal and daily fluctuation. It could be argued that a safety factor is implicit within NFPA 13. But to save everyone’s time and scrutiny, a simple 5 PSI or 10% safety factor tends to be common practice. Too high a safety factor isn’t necessarily a good thing because it could lead to needing a fire pump that introduces many new points of failure or could add unnecessary cost to a system.
 
18. Does your department conduct flow tests, can we conduct a flow test, or are those done by the water department?
  → Note: This is just practice-based by jurisdiction. Some don’t allow flow tests at all and use water modeling (California).
 
INSPECTOR'S TEST*
19. [If there are only wet systems] We usually locate the inspector’s test at the riser, which NFPA 13 allows for wet systems. Do you require it to be located remotely?
  → Note: If this is a dry or pre-action system, then the inspector’s test must be remote. If it’s wet, it’s allowed to be at the riser. That said, some jurisdictions have a preference which we’d want to accommodate here.
 
WATERFLOW*
20. Do you want a horn/strobe, or electric bell on the outside of the building for waterflow?
  → Note: Just a jurisdictional preference. Either of these are easier to accommodate than a water motor gong which had been the tradition for some time.
 
21. Is exterior access required for the sprinkler riser room?
  → Note: These are usually on the outside of the building since the water service entry cannot go more than 10 ft underneath the building without open trenches, per NFPA 13, but sprinkler riser rooms don’t always have an exterior door.
 
SITE
22. Just a few more questions. Do you require a post-indicating valve? There are no code mandates for one.
  → Note: Some jurisdictions want them, many don’t care. Just an opportunity to coordinate it early here.
 
23. Is Fire Flow ok to be determined using the International Fire Code Appendix B, or do you have some other method to calculate it?
  → Note: Fire Flow is wildly misunderstood and falls through the cracks of design scope. As a result, many jurisdictions don’t pay attention to it or aren’t familiar with it. If they don’t know or don’t care, Appendix B is a fine approach to use.
 
FIRE PUMP*
24. We have a fire pump on this project. Do you consider the electric power supply to be Reliable or not?
  → Note: NFPA 70 has specifics on how power is considered to be reliable or not. There are formal definitions, but it’s up to the AHJ on whether they consider the power utility at the site to be reliable or not. If it’s a point of contention or needing clarification, it’s worth spending time here because the cost to go from an electric fire pump to a diesel or add a generator can be substantial.
 
STANDPIPES*
25. We intend to have a [wet/dry manual/semi-automatic/automatic] standpipe system for this building, using [Class I 2½” / Class II / Class III] hose connections.
  → Note: In sticky projects using dry standpipes or high-rises, the type needs to be coordinated. In basic non-high-rise situations, a wet manual system is fairly straightforward, so it’s not a question as much as a coordination point.
 
26. We intend to locate hose connections on the floor level landings of stairs. Is that acceptable?
  → Note: The IBC and NFPA 14 have jogged back and forth on this, but they now correlate on the main-floor-level landings of stairways for hose connections. AHJs are permitted to require intermediate-level landings in both the IBC and NFPA 14, though, so it’s an important coordination point.
 
Thank you SO much for your time. Any questions for me, or anything else you feel I should have asked?


YOUR TURN
Alright - it's all out there - what would you tweak?

If you’re an AHJ, how can I better ask the question?

How can I better clarify the intent of the question?

What am I missing? Would absolutely love your commentary below. Your input can make this new collaborate tool much more helpful and hopefully impactful for the industry as we launch it and hopefully move things forward.

See you in the comments 
↓↓

- Joe 

14 Comments
gregory riley
12/3/2025 11:26:03 am

Awesome list. Thanks for sharing.

Reply
Steven W Dube link
12/8/2025 12:04:03 pm

BRIEF INTRO
Thanks for taking my call. I’m Joe Meyer, designing the [project] at [address]. It’s going to have [fire alarm/sprinkler/standpipe system(s)], and I’d like to ask you a few questions to make sure we’re coordinated with your department. Should take about five minutes. Is that OK?
→ Note: If the time isn’t good, or they’d prefer an email, I’d go that route instead.

APPLICABLE CODES & STANDARDS
1. Great. Your website says you’ve adopted the [2012/2015/2018/2021/2024 IBC or NFPA 101], is that correct?
→ Note: Doing the research ahead of time is key. Without it, it makes the listener feel like they’re doing the work.

Before hand yes, and email much better

2. Do you adopt any specific editions of NFPA standards like NFPA 13, 14, or 72, or just whichever edition is referenced by your building code?
→ Note: Many people don’t know this, but IBC Chapter 35 and NFPA 101 Appendix D or E will actually list which editions of NFPA standards are referenced. Some jurisdictions will adopt very specific editions, which is why I like to ask the question here.

Following questions noted with an asterisk (*) are only asked if necessary.

Good point, in NH everyone is suppose to use the NH State Fire Marshal's Office adopted codes and nothing less.

FIRE ALARM*
3. For fire alarm, we intend to locate the main control panel in [front entry/main electrical room/a back of house area]. If we do so, do you require an annunciator panel at the building’s front entry?
→ Note: For small buildings with one main entry where the FACU is located near the entry, no annunciator is usually needed. For larger or more complex buildings, when we might not want the FACU at the front entry, having an annunciator at the front is a very reasonable need.

Yes! Keep it simple- and together for that Firefighter Station

4. Does the fire alarm monitoring require a listed Central Station Service, or is standard code-required monitoring, like a supervising station, acceptable?
→ Note: Jurisdictions that require a listed Central Station service usually know what it is, and will recognize that it’s required. It’s more expensive and carries more stringent requirements than a normal supervising station, which is a code-minimum requirement.

Chief's discretion

DUCT DETECTION*
5. When duct detectors are needed, do you simply require locations to be per [the IMC/NFPA 90A], or do you require duct detectors to be located in specific locations, like the supply or return side of units in the ductwork?
→ Note: This is a question I could use help with. A simple ‘per code’ answer is wanted here, but some jurisdictions have insisted on locating duct detectors on the supply-side of units, or return-side, or both. If the jurisdiction has a specific requirement, I’d like to know that now rather than be surprised later, but most usually don’t, and as a result, it’s a lame question to ask in those cases.

After filters always, not both

6. Do you require duct detectors to initiate an alarm signal, or is it OK to have those report a supervisory signal to the fire alarm control panel?
→ Note: NFPA 72 allows duct detectors to initiate a supervisory signal, because they’re more prone to nuisance alarms than other devices. An alarm signal usually results in a truck rolling up to the building each time. Jurisdictions that are familiar with this topic are usually more than happy to have duct detectors on supervisory rather than alarm.

Alarm


7. When a duct detector activates, can it shut down just that unit or do you require all units to be shutdown?
→ Note: To my understanding, this is just a preference. Not a huge deal either way unless we’re talking about a massive building or building complex where all units shutting down would be very uncomfortable and problematic.

Individual shut downs

SECURITY / KNOX BOX
8. Do you require a Knox Box?
→ Note: There’s likely a code path for this, but it’s not something I’ve hunted down to date. Most jurisdictions can readily answer this.

Knox Box of relevant size to number of keys at Maste Box, front entrance

9. Is the Knox Box required to tie to the fire alarm system?
→ Note: These can be monitored by the fire alarm system. Most jurisdictions don’t require them to be monitored, but some will in areas that have higher crime rates.

Up to building owner

FIRE SUPPRESSION - FIRE DEPARTMENT CONNECTION*
10. Do you mandate a maximum distance from a fire department connection to a nearest hydrant?
→ Note: Some jurisdictions care, others less so. There’s (to my knowledge) not a mandated distance, but some jurisdictions will require as close as 50 ft and others as far away as 400 ft.

200Ft

11. Can the FDC be mounted on the building’s street-facing exterior wall, or does it have to be located r

Reply
Jocelyn Sarrantonio
12/3/2025 11:31:57 am

I heartily second the suggestion that you do the research ahead of time, so it's framed as mostly yes/no questions.

As a millennial who is allergic to talking on the phone, I usually attempt to ask the first few questions over email to make sure I'm talking to the right person, but this IS one case I have to admit that a phone call is usually better. Folks may be hesitant to put too much in writing, but they'd be more than happy to talk on the phone. You build a rapport, and get a read on what sorts of things are very important to them. It's best to follow up with an email, as a record of understanding for the conversation.

You may also have to talk to multiple people to get your answers. (cringe)

And not to open a whole can of worms, but one thing I would add is figuring out what a local jurisdiction's requirements are for emergency responder radio coverage systems (ERRCS).

Reply
Mike Morey
12/3/2025 11:40:47 am

Joe,
Another winner of an idea. A few items for thought, feel free to reach out offline also:

FDC - do we still need to ask for thread for 2 1/2s? I haven't seen a non-NST in a LONG time but there used to be a lot of big cities with their own threads

Backflow - may want to create a "water purveyor" section as arguably these questions are most likely going to be in their court, but the AHJ may be willing to direct you.

Fire pump - (may also cross over to water purveyor) do you require a low suction control valve

Standpipes - if manual what size pumper truck would respond, might be worth calling out to users of said list where they can find the rating methodology for a pumper truck which I can look up but isn't in front of me


Reply
Bobby V
12/3/2025 01:23:01 pm

Most major cities' development department websites list their current adopted codes and standards, IFC/IBC code amendments, and "code interpretations/code bulletins" papers, etc. And like the article mentioned, the local water purveyor may have requirements for backflow preventer location. The answers to most of these questions can be found by researching all of these resources. Great article!

Reply
Joe Meyer
12/3/2025 02:49:19 pm

If I can find it there, I will! I've had only a small handful of jurisdictions have everything posted online. I love that part of code research beforehand.

Even so though, some things are project specific (FDC location and equipment placement come to mind) and still worth the call. It sure makes the questions a whole lot shorter when it is posted online!

Reply
Ed Kramer
12/3/2025 03:55:41 pm

Awesome list, Joe! A few more questions to consider:

a) Great, you've adopted the xxxx edition of the IBC. Have you adopted any local amendments that I need to be aware of?

b) Great, you use a x" Storz. Do you require a straight Storz, or one with a 30 degree elbow?

c) For a manual standpipe calculation: Do you have a maximum inlet pressure (such as 150 psi) at the FDC?

d) For electric fire pumps, does the local electric utility require a soft-start controller?

Yea, I've been burned on all of these!

And a couple of standard/code references that address maximum distance of a standpipe FDC from a hydrant/street: NFPA 14 section 7.12.2.3 and IFC section 507.5.1.1.

Reply
Bill J
12/3/2025 04:10:30 pm

The views I express on this site are my own and do not reflect any official view or position of the LAFD. I'm not a spokesperson for LAFD, nor am I trying to me; these are just my thoughts from my own personal experiences after 10+ years with the Department.

Definitely do your research. In our jurisdiction, our state adopts the IBC/IFC and adds state-level amendments, and then we take those documents and add local amendments. The final product is in many respects identical to the underlying IBC/IFC, but the differences when they occur can be significant. Likewise, knowing in advance which edition of which code or referenced standard is authoritative and how the AHJ intends to resolve any hypothetical conflicts among them will save you headaches later.

Also, before engaging with an AHJ on a specific project, you may consider taking a moment to get the lay of the land. Some jurisdictions split subject matter between departments (e.g. fire vs. building and safety), and sometimes between different groups within the same department. Few things will irritate a busy AHJ faster than when "I just have a quick question" turns into a 30-60 minute conversation. Being able to pare your questions down to just those within the purview of the specific person with whom you are speaking is a quick and easy way to make friends with your AHJ.

Another question worth asking is what scopes of work qualify for an over-the-counter review, what the typical review time is for those that don't, and whether or not an expedited review option is available (anticipate an additional fee). We all have timelines to manage and projects to balance, so having a realistic idea about this at the start of yours will help you manage your client's expectations.

The list as provided is both comprehensive and well written. Nicely done.

Reply
Joe Meyer
12/3/2025 04:17:51 pm

The worst part of this list, in my opinion, is that it's so long.

For most projects, code research, past experience, or losing alarm, sprinkler, pump or standpipes, it should pair it down significantly. Like Bobby said - if it's posted somewhere, then it's 100% something I don't want to re-ask. Open items only.

Thank you so much for the perspective Bill!

Reply
Alan Zimmerman
12/6/2025 07:33:53 am

In regards to backflow preventers, when detector double check or RPZ is required the following questions should always be asked:
1. Who supplies the by-pass meter? Installer or Water Department
2. If the Installer, how is the bypass meter units to read? Gallons or Cubic Feet

Reply
Kevin Bergstrom link
12/7/2025 11:57:30 am

Great post Joe. As an AHJ I have received this call countless times and I assure you that the person answering the call is often experiencing the same fear, anxiety and imposter syndrome symptoms that you are. "What if they ask a question I don't know the answer to?" "What if I sound like a fool?" We are all human so your post is incredibly relatable. My approach to these calls is to try and provide as much information as I can, let the caller know that I will get back to them on the items that I am unsure and follow up as soon as possible. There should be no secrets or surprises for either party.

For item #8 "Do you Require a Knox Box?" the code path is pretty simple. The IFC chapter 506 'Key Boxes' provides the AHJ the authority to require a key box to be provided on any building where it is determined immediate access is necessary. The AHJ can determine the type, size and location of the key box and most agencies require them on any building with fire service features that may initiate our response such as a fire alarm control panel.

The 'Code Call' is an essential part of the process to make sure the project moves forward with as few setbacks as possible.

Reply
Chris Mcdaniel
12/7/2025 01:38:22 pm

AHJ here and this list of questions you have put together are not only amazing but usually wanted. I cant tell you how long I've been dying to even have 1 contractor make any contact with me and ask any of these questions. 100% of the time I'm calling the GC or fire protection contactor up giving them the list.

Reply
Joseph Davila
12/10/2025 11:46:57 am

Newer fire code official here,
One of the things I truly enjoy is collaborating on projects, I have been the one to initiate these code calls when examining plans to gain better insight into a project. My biggest pet peeve, however, is when I am asked, "how do you want me to design this or that?". I have 19 years of sprinkler and fire alarm experience run concurrently with my 32 years as a career firefighter and hold a NICET III but as the AHJ, my job is not to design, only confirm that the intent of the code is met. There are sections of the IFC that clarify, "or per AHJ request" and I will happily make suggestions to work out a problem but sans that language in the IFC, I would prefer that the designer actually review the code prior to making that code call as my responses will most likely be, "meet the code requirement". This is a great article! and I sincerely wish that the "silos" which exist in our world would disappear as we are all trying to achieve the same goal. Open and honest communication and collaboration should be welcomed by all!

Reply
Dave
12/10/2025 12:33:52 pm

Over time, I’ve been re-editing my response to this great post (and I will probably wish I can edit further after posting), but in the meantime everyone has brought up REALLY good points; thumbs-up to all. I have never had a hostile reaction from an AHJ. See? Even AHJ’s can share our fears (Kevin). One of the best lessons I learned from a former boss is that it’s all about the relationships. Simple, but so true. I guess as long-in-the-tooth as I am, I am now only 50% nervous making a cold call. (That Dale Carnegie Course decades ago helped.) Keeping it friendly, maybe check ahead of time who I will be talking to, see if we have any mutual background. Try not to call Friday afternoon nor during the week prior to Independence Day. I could leave the call to one of my newbies, but I want to be the face of the phone call. Being on the engineering side, I sometimes lead with our mutual goals of clarity in bids docs, level playing field, trying to avoid confusion & delay, and change orders. Like Jocelyn, I often send an email first explaining my follow-up phone call. While I do keep an AHJ database, it need updating all the time, and sometimes people change. While it would be good for my database to ask ALL these questions in one phone call, I will usually limit it to what is relevant to that particular project (“it’s too long” - Joe). And if it’s going well, then I’ll ask more. I might ask about standpipes for example, next time. Civil has the FDC? I’ll let them worry about it for now. I usually check the municipal code to see if there have been any amendments. I pre-check if there is GIS mapping data or websites for identifying water purveyor. Of course take notes, save and date any answers given!

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET THE TOOLKIT

    SUBSCRIBE

    Get Free Articles via Email:
    + Get calculators, tools, resources and articles
    + Get our PDF Flowchart for Canopy & Overhang Requirements instantly
    Picture
    + No spam
    ​+ Unsubscribe anytime
    I'm Interested In:

    AUTHOR

    Joe Meyer, PE, is a Fire Protection Engineer out of St. Louis, Missouri who writes & develops resources for Fire Protection Professionals. See bio here: About


    FILTERS

    All
    Announcements
    Author Jocelyn Sarrantonio PE
    Book Review
    Calculators
    Career
    Course
    Delegated Design
    Design Challenge
    Detail Critique
    Fire Alarm
    Fire Events
    Fire Suppression
    Flammable & Combustible Liquids
    Flexible Drops
    Floor Control Valve
    Life Safety
    News
    NICET
    Passive Fire Protection
    PE Exam
    Perspective
    Pick A Part
    Pick-A-Part
    Products
    Site Updates
    Special Hazards
    Specifications
    Sprinkler Systems
    Standpipes
    Tools
    Videos


    ARCHIVES

    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    January 2025
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    December 2020
    November 2020
    October 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    April 2018
    March 2018
    February 2018
    January 2018
    December 2017
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    May 2017
    April 2017
    September 2016
    August 2016
    July 2016
    June 2016
    July 2015
    June 2015
    May 2015

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT